By Michael Gardner
![]() |
Code Compliance
The NBCC 2006 requires all firewalls to meet the following design criteria:
They must be continuous from the foundation and continue through the roof to form a parapet, and
They must allow for the collapse of the construction on the side of the wall exposed to fire while remaining intact to protect the structure on its opposite side.
The NBCC 2006 permits the use of gypsum area separation wall systems where two-hour fire resistance and sound attenuation of 50 or greater are required.
The System
Solid gypsum board firewalls use three basic components:
25mm (one inch) thick type X gypsum board liner panels that are 610mm (two feet) wide and either 2440mm, 3050mm, 3660mm, or 4270mm (8, 10, 12 or 14 feet) long.
Metal framing members, consisting of 50mm (two inch) wide H-studs and U-shaped track.
"Break away" L-shape aluminum clips that soften at relatively low temperatures.
The area separation wall is attached to the adjacent building's structural framework using L-shaped aluminum clips, which are fastened to the area separation wall's steel H-studs and the structure of the townhouse. The clips connect each H-stud on both sides with the adjacent floors or roof/ceiling intersections to keep the area separation wall in place between the two structures.
The aluminum L-clips are manufactured to soften at about 600°C (1100 °F). Consequently, when they're exposed to the heat of a fire on one side of the area separation wall, they break away between the steel and the wood frameworks and allow the burning structure to fall away while leaving the area separation wall in place.
Because the gypsum board panels prevent the heat on the "fire side" from reaching the opposite side, the aluminum clips supporting the wall on the non-burning side remain intact and prevent the fire from spreading.
Aluminum clips used to connect gypsum area separation walls to adjacent buildings must be specified in the tested design to ensure that they perform properly during a fire. Clips must be fastened and installed in conjunction with system directions.
Michael Gardner is Executive Director of the Gypsum Association.